Analisis Arrester Sebagai Sistem Proteksi Pada Transformator di Gardu Induk Keramasan

Authors

  • Hermawanto Hermawanto Universitas PGRI Palembang
  • Irine Kartika P Universitas PGRI Palembang
  • Perawati Perawati Universitas PGRI Palembang
  • Yudi Irwansi Universitas PGRI Palembang

DOI:

https://doi.org/10.55606/jtmei.v3i3.4192

Keywords:

Arrester, Transformer, and Distance

Abstract

Lightning overvoltage is a periodic overvoltage caused by external causes. An arrester is equipment that protects installations from overvoltage disturbances due to lightning strikes or electrical surges. The transformer functions to distribute electrical power by increasing or decreasing the voltage at the substation. This research focuses on substation equipment, namely the type 3EP 2150-2PL3 arrester connected to a 100 MVA IBT Transformer. Good protection is obtained if the arrester is placed as close to the transformer as possible. Therefore, this distance is determined so that protection can take place properly. The distance between the arrester and the transformer used at the Keramasan 150 KV substation is 5 m. while from the calculation results it is 22.5 m. based on SPLN 7: 1978 that for a 150 kV system the distance between the lightning catcher and the transformer does not exceed 80 m. This means that the distance between the arrester and the 100 MVA IBT Power Transformer is still within the limits set by PT PLN. The continuity of the spark that occurs in the arrester is still within safe limits and in accordance with mathematical analysis.

 

 

Downloads

Download data is not yet available.

References

Agustian, R. (2018). Analisa penempatan jarak arrester sebagai proteksi transformator terhadap tegangan lebih surja petir. EPSILON: Journal of Electrical Engineering and Information Technology, 16(1), 5–8.

Azis, A., & Nurdin, H. A. (2020). Analisa jarak lindung lightning arrester terhadap transformator daya 20 MVA gardu induk Sungai Juaro Palembang. TEKNIKA: Jurnal Teknik, 7(1), 106–120.

Febrianti, I. K. (2017). Analisa penurunan faktor kerja transformator daya 30 MVA. Jurnal Ampere, 2(1), 18–22.

Ginting, Y. T., Napitupulu, J., & Pane, A. G. A. (2021). Simulasi tegangan induksi kabel akibat arus petir pada kawat penangkal petir. JURNAL TEKNOLOGI ENERGI UDA: JURNAL TEKNIK ELEKTRO, 9(2), 115–122.

Handoko, S. R. (2023). Analisa penggunaan lightning arrester (LA) pada sistem tenaga listrik gardu induk 150 kV PLTU Rembang (Doctoral dissertation, Universitas PGRI Semarang).

Hibatuillah, M. (2022). Analisa efisiensi transformator daya 11/150 kV 54 MVA melayani beban pada PLTGU Unit 1 PT. PLN (Persero) UPDK Keramasan Palembang (Doctoral dissertation, Politeknik Negeri Sriwijaya).

Husna, N., Jie, S., Zulkaidah, W. O., & Teknik Elektro, U. H. O. (n.d.). Analisis penggunaan arrester sebagai pengaman transformator dari sambaran petir.

Hutauruk, T. (1991). Gelombang berjalan dan proteksi surja. Erlangga.

Ichsan, R. (2015). Analisa pemasangan jarak antara arrester dan transformator daya di gardu induk Boom Baru PT. PLN (Persero) Palembang (Doctoral dissertation, Politeknik Negeri Sriwijaya).

Kolompoy, A. L., Patras, L. S., & Mangindaan, G. M. C. (2022). Analisa koordinasi isolasi arrester pada transformator di gardu induk Paniki 150 kV.

Labado, R., Mujiman, M., & Pambudi, P. E. (2015). Analisis penempatan arrester terhadap efektivitas proteksi transformator pada PT. PLN (Persero) P3B Jawa-Bali APP Salatiga gardu induk 150 kV Bantul. Jurnal Elektrikal, 2(2), 79–87.

Manihuruk, J., Simorangkir, T., & Sitanggang, N. L. (2021). Studi kemampuan arrester untuk pengaman transformator pada gardu induk Tanjung Morawa 150 kV. Jurnal ELPOTECS, 4(1), 16–25.

Nasution, R., Yusmartato, Y., & Armansyah, A. (2019). Analisa penempatan lightning arrester sebagai pengaman gangguan petir di gardu induk Langsa. Buletin Utama Teknik, 14(3), 205–209.

PT PLN. (1978). Standar Perusahaan Listrik Umum Negara SPLN 7: 1978 tentang pedoman pemilihan tingkat isolasi transformator dan penangkap petir.

Saragih, R., Yusniati, Y., Nasution, R., & Armansyah, A. (2020). Studi peralatan proteksi sambaran petir lightning arrester pada jaringan distribusi 20 kV. JET (Journal of Electrical Technology), 5(1), 32–37.

Shoimatussururoh, S. (2022). Pemeliharaan lightning arrester (LA) pada gardu induk Saketi 150 kV di PT. PLN (Persero) ULTG Rangkasbitung. INSOLOGI: Jurnal Sains dan Teknologi, 1(5), 520–531.

Sogen, M. D. T., & ST, M. (2018). Analisis pengaruh ketidakseimbangan beban terhadap arus netral dan losses pada transformator distribusi di PT PLN (Persero) Area Sorong. Jurnal Electro Luceat, 4(1).

Published

2024-08-09

How to Cite

Hermawanto Hermawanto, Irine Kartika P, Perawati Perawati, & Yudi Irwansi. (2024). Analisis Arrester Sebagai Sistem Proteksi Pada Transformator di Gardu Induk Keramasan. Jurnal Teknik Mesin, Industri, Elektro Dan Informatika, 3(3), 178-`187. https://doi.org/10.55606/jtmei.v3i3.4192